The AIP9613X AC ground resistance tester supports 50/60 Hz dual-frequency output and features high-precision ground resistance testing, intelligent alarms, and multiple safety protections. It complies with GB and IEC safety standards.
High-precision testing: High-speed MCU + hardware feedback ensures stable and reliable test results.
Dual-frequency output: Supports AC 50Hz/60Hz output, adapting to global testing standards.
Intelligent parameter settings: Test current and resistance upper and lower limits can be freely set, and test results are displayed in real time.
High-definition LCD interface: intuitive operation and convenient parameter configuration.
Audible and visual alarm function: Automatically determines whether the product is qualified or unqualified and issues an alert for any abnormalities.
Multiple safety protections: It has automatic overvoltage and overcurrent protection to improve the safety of equipment and personnel.
Standards Compatible: Complies with multiple safety standards such as GB4706.1, GB4943, IEC60335-1, and IEC60950.
MCU intelligent control technology: precisely controls the current boosting process, improving test repeatability and stability.
Hardware closed-loop feedback: Real-time correction of output current and resistance to ensure measurement accuracy.
Dual-band AC output: Meets the testing requirements of the international market for 50Hz/60Hz products.
Intelligent upper and lower limit determination: Automatically judges test results, reducing human error.
Multiple protection mechanisms: Automatic overvoltage and overcurrent protection to ensure continuous and stable operation.
International standards compliant: Meets GB and IEC safety certification testing requirements, suitable for export product testing.
| AIP9613X | |
| Input voltage | 220V±10% |
| Input frequency | 50/60Hz±5% |
| Fuse | Fuse 5A/250V |
| Grounding resistance test | |
| No-load output voltage | <12VAC |
| Output current range | AC 5~32A |
| Output current accuracy | ± (1% of the set value) |
| Output current stability | Less than 0.3% (10A/100 mΩ) |
| Output frequency range | 50Hz/60Hz |
| Output frequency accuracy | ± 0.2%, user selects. |
| Grounding resistance test range | 5-600 mΩ (5-10A); 2-200 mΩ (11-25A); 2-150 mΩ (26-32A); |
| Grounding resistance test accuracy | ± (2% of the measured value) |
| Test time range | 0.5-999.9s |
| Test time resolution | Resolution 0.1s, 0 seconds for continuous output |
| Functional parameters | |
| Display Interface | 16*2 Blue Screen Character LCD Display |
| Communication interface | PLC, RS232 (optional) |
| Correction method | Software calibration can be performed by inputting parameters via the front panel. |
| Work environment | 0-40℃, 20-80%RH |
| External dimensions | 280mm(W)×89mm(H)×370mm(D) |
| Random accessories | Power cord ×1, test clips ×2, fuse ×1, instruction manual ×1 |
| Weight | 12KG |